SEI Telephony Products
ISDN Premises Power
SEI Telephony Products
NT1's
PoweRack SERIES
DP SERIES
1145 REPLACEMENTS
BATTERY PACKS
STAND ALONE
ISDN DISTR. BAYS
1145 Direct Replacements

S1145B Battery Pack

The S1145B is an improved direct replacement for the following Lucent/AT&T ISDN battery packs: 1147B1, 1148B1, 1149B1, and KS-21906. Features include 8 amp hour battery capacity and compatibility with the existing wall mounting plate and connection wiring.

The S1145B microprocessor-based controller monitors charge status and automatically performs a periodic battery test to guarantee the holdover capability of the pack. Additional features include a Manual Battery Test Switch and LED indicators for Battery Charge Status and the Battery Test Status.

The S1145B contains four 12 volt, 8 Amp-hour sealed lead acid batteries connected in series to provide a nominal 48 Vdc. A panel-mounted fuse protects the output. Note that the S1145R is the companion power unit for S1145B battery pack.

S1145B Battery Pack

 

Ordering Information
MODEL # DESCRIPTION DIMENSIONS
(W"xD"xH")
S1145B
8 amp hour external battery pack, direct replacement for Lucent/ATT 114X
11.4 x 8.8 x 4.5


Technical Specifications
ELECTRICAL
  • Nominal Output Voltage: 48 Vdc
  • Maximum Output Current: 6.25 A max.
  • Recommended Charge Voltage: 54.0-55.2 Vdc
  • Rated Capacity: 8 Amp-hours
 
ENVIRONMENTAL
  • Temperature: -20° C to +40°C
  • Humidity: 95% non-condensing
Optimum battery life will be achieved if the unit is operated at a temperature of 25 deg C.
 
LED INDICATORS

Battery Charge Status:

  • Constant Green - Fully Charged
  • Flashing Green - Charging
  • Constant Red - Improper Charging Voltage

Battery Test Status:

  • Constant Green - Battery Good
  • Fast Flash Red - Wait, Then Test
  • Slow Flash Red - Replace Battery
 
USER INTERFACE

Manual Battery Test Switch – Push to Test

NOTE: The Manual Battery Test switch is disabled when the battery is charging. Also, to prevent unnecessary battery discharge, the Manual Battery Test is disabled for 5 minutes following a Battery Test. In both cases, the Wait, Then Test indication is displayed.


For order information or technical support call us at >> 800-765-4734, or email us using our Contact Us page


    >  RELATED FILES

Online Powering Guide
A complete technical overview of ISDN premises powering.

S1145B Product Information Sheet
S1145 Installation and Operations Manual

System Engineering International, Inc. • 5115 Pegasus Court • Suite Q • Frederick, MD 21704
Voice: (301) 694-9601 • Fax: (301) 694-9608 • Email: info@seipower.com