ISDN Premises Power
SEI Telephony Products
POWERACK SERIES
DP SERIES
1145 REPLACEMENTS
BATTERY PACKS
STAND ALONE
ISDN DISTR. BAYS
PoweRack Series

PoweRack 180

The PR180 is a premises powering unit that integrates NT1 caging, dual 48 volt DC power supplies, and battery backup in a single unit for powering ISDN telephones and Lucent D-300 circuit card NT1's. The PR180 will house and power up to seven D-300 circuit cards and provide power for up to 180 phones in a multipoint mode. Connections from the service provider are done with standard 25 pair amphenol connectors. Distribution to the terminals is accomplished via standard 8-pin modular connectors. All power to the terminals and NT1s are protected by solid state thermal fusing. System operation is maintained after loss of commercial power by the companion BP180 battery packs, which slide on to the PR180 and fasten to the wall or rack. During extended periods of utility outage the batteries are protected from over-discharge by the built-in low voltage detector and disconnect circuit. The PR180 comes with an integrated battery test feature; remote monitoring is provided by a contact closure that can be interfaced to a remote alarm unit.

All PR series units are mountable either on a wall or on 19" racks. Mounting brackets for 23" or 25" racks may be ordered as options (specify 23RM or 25RM after the model number).

PoweRack 180

NT1 When NT1's are purchased with a PoweRack 180, SEI will install and individually test each NT1, providing the customer with a fully configured solution suitable for immediate installation.

Ordering Information
MODEL # DESCRIPTION DIMENSIONS
(W"xD"xH")
PR180-8 PoweRack with 1/2 hour battery for 7 D300 NT1's and 180 Phones 19 x 9 x 28
PR180-24 PoweRack with 2 hour battery for 7 D300 NT1's and 180 Phones CALL

Technical Specifications
Electrical
Input Voltage 120 VAC +10%/-15%
(240 VAC Factory Option)
Output Voltage 42-56 VDC
 
Environmental
Temperature -20° C to +40° C Humidity 95% non-condensing

Optimum battery life will be achieved if the unit is operated at a temperature of 25 deg C.
 
NT1 Compatibility
D-300, P-230
 
Standards
UL 1012, CSA 234

 


For order information or technical support call us at
800-765-4734
or email us using our Contact Us form


      > RELATED FILES
Download pdf Product Information Sheet
Download pdf Power Supply Adjustment Procedure

System Engineering International, Inc. • 5115 Pegasus Court • Suite Q • Frederick, MD 21704
Voice: (301) 694-9601 • Fax: (301) 694-9608 • Email: info@seipower.com